Specification
GENERATOR
Type
Dual Voltage (Manual parallel)
Frequency (Hz)
50 / 60
Output (kVA)
200 / 220
Output (kW)
160 / 176
Voltage (V)
200/400 / 220/440
Current (A)
577/289 / 577/289
Single-phase auxiliary output: Voltage (V)
100 / 110
Single-phase auxiliary output: Dedicated terminals (kVA)
-
Single-phase auxiliary output: Outlets (kVA)
1.5×4 / 1.65×4
Power factor (%)
3-phase 80 (lagging) / Single-phase 100
ENGINE
Make, Model
MITSUBISHI 6D24-TLE2B
Type
Direct-Injection, Turbo-Charged, Intercooled
Rated output (kW)
181 / 199
Rated output (PS)
246 / 271
Rated speed (min-1)
1500 / 1800
Fuel tank capacity (L)
390
Engine oil amount (L)
37
Battery × quantity
170F51×2
DIMENSION & WEIGHT, etc
L×W×H (mm)
3700×1300×1670
Dry weight (kg)
3240
Operating weight (kg)
3630
Sound power level in decibels (dB)
93 / 94
Sound pressure level (dB[A])
65 / 65
Designated emissions regulation
JPN Stage 2
ā—¸Specifications are subject to change without notice.
Inquiry - Airman 220 KVA Generator - SDG220S-3A6